  395   29 Sep 2017, 14:46 Andreas KochGeneralInformationWP74 - OCD contacts for this weekend

30.09. from 08:00 until 01.10. 08:00 - Andreas Koch 9-6443

01.10. from 08:00 until 02.10. 08:00 - Joakim Laksman 9-5630  

  3   03 Nov 2016, 12:58 Alessandro SilenziXTD2InformationCurrent PLC-Karabo Conflict

Tobias Freyermuth and me worked on the system and as of last night, we found two new issues between Karabo and the PLC interlock:
 - one is a Karabo issue from the Interlock PLC interaction, the Karabo device waits for a PLC response that does not come when the PLC is interlocked (i.e. Karabo wants to open a valve but the PLC correctly refuses and ignores the command)


 - one is a PLC issue, the interlock is not triggered in all cases after testing (e.g. a ion pump out of set point does not closes a gate valve closure as specified).

The first one was reproduced with the BeckhoffSim simulation. It can therefore be fixed by CAS without dependencies from AE (except for the next integration test).

  7   04 Nov 2016, 18:08 Alessandro SilenziGeneralInformationBeckhoffDevices back to responsive

 I reproduced the behaviour of the PLC on beckhoffSim. This reproduces the same behaviour seen in the tunnel devices (devices hang).

Implemented the fix and verified the correct behaviour with beckhoffSim.

Fixes will be verified next Monday with the tunnel system.

Have a nice weekend

Alessandro

 

ps: For future reference:

beckhoffSim  tags/1.1.0-1.4  (implements the recent plc behaviour (framework tag N/A Could not find tobias))

beckhoffDevices tags/2.0.1-1.4 hangs

beckhoffDevices tags/2.0.2-1.4 does not

 
  8   07 Nov 2016, 19:15 Alessandro SilenziXTD2InformationKarabo Installation back to normal

 Karabo to PLC communication has been tested successfully in the SA1 Vacuum installation.

in attachment:

OK.png -> Initial Status, all OK

interlocked.png -> pump P10300I is turned off -> Setpoint -> off -> Valve automatically close and set "Interlock OK" to false

afteron.png ->  pump P10300I is turned on again but-> Setpoint -> off -> Valve automatically close and set "Interlock OK" to false

backToNormal.png -> Like initial status but valves stay closed

 
Attachment 1: OK.png
OK.png
Attachment 2: interlocked.png
interlocked.png
Attachment 3: backToNormal.png
backToNormal.png
Attachment 4: afteron.png
afteron.png
  25   24 Jan 2017, 18:36 Alessandro SilenziGeneralInformationMore items in the master equipment list

Master Component list is being updated.

https://docs.xfel.eu/share/proxy/alfresco/api/node/content/workspace/SpacesStore/1c6c10cd-d741-410d-bd05-bb00944514dc/MasterEquipmentList.xlsx?a=true

Best regards

Alessandro

  45   12 Feb 2017, 14:02 Alessandro SilenziGeneralProblemCurrent Status

 Vacuum loop:

- Interface between PLC and Karabo is not functioning.

The fault currently resides in the PLC behaviour, the self-description sent out is badly formatted (due to a buffer overrun)

The misbehaviour is confirmed, the PLC TCP Client from AE is also ailed by the same problem.

Motion Loop:

- As of Friday, the motor parameters were not completely sent to AE. In attachment the data collected by N. Jardon (AE). Input needed for PSLIT motors.

 

 

 

Attachment 1: Motors_Parameters.xlsx
  46   14 Feb 2017, 09:59 Alessandro SilenziGeneralProblemBeckhoff loop status

2017.02.13 19:30 Status:

- Self-Description back in shape.

- Bad SelfDescription reproduced in BeckhoffSim (Karabo implemented PLC communication) and solved in BeckhoffCom (Karabo "PLC Client").

- The build status of the Firmware is not ok. roughly 90% of the PLC soft devices are in error. It is a fault in the automatic Firmware build procedure.

Nerea and Jan will work on this until it is fixed.

 

  47   15 Feb 2017, 20:10 Alessandro SilenziGeneralFeedbackCurrent Vacuum Status

The PLC is still not completely error free.

It is considerably better performing than the last days:

the current average pressure as measured by the Ion Pumps is 4.21e-09 mBar

there are Currently 96 ion pumps in the Tunnels as seen by the PLC:

3 cannot properly communicate with the PLC

SA1_XTD9_VAC/IPUMP/P10510I

SA1_XTD9_VAC/IPUMP/P11130I

SA1_XTD9_VAC/IPUMP/P12120I

3 have an ambiguous control name:

SA1_XTD2_VAC
SA1_XTD9_VAC2
SA1_XTD9_VAC0
 

And 4 have no channel assigned in the Karabo inteface (CAS to solve this)

SA1_XTD2_VAC/IPUMP/P10340I
SA1_XTD2_VAC/IPUMP/P10350I
SA1_XTD9_VAC/IPUMP/P10370I
SA1_XTD2_VAC/IPUMP/P10360I

The remaining 86 replied and:

Average pressure is  4.210e-09 mBar

Maximum pressure is  2.60-08 mBar

Minimum pressure is  8.90e-10 mBar

Attachment 1: 20170215Vacuum.txt
SA1_XTD9_VAC/IPUMP/P12180I 0x6009 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P10510I 0x6009 no data
SA1_XTD9_VAC/IPUMP/P11110I 0x6007 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11130I 0x6007 no data
SA1_XTD2_VAC/IPUMP/P10200I 0x6007 2.5999999930803597e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C10901I
SA1_XTD2_VAC/IPUMP/P10270I 0x6007 5.500000010982831e-09
no channel number defined for {} SA1_XTD2_VAC/IPUMP/P10340I
SA1_XTD2_VAC/IPUMP/P10030I 0x6007 8.899999626166277e-10
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11403I
SA1_XTD2_VAC/IPUMP/P10180I 0x6007 2.5999998598535967e-08
SA1_XTD9_VAC/IPUMP/P11010I 0x6009 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11330I 0x6009 2.5999999930803597e-09
SA1_XTD2_VAC/IPUMP/P10220I 0x6007 3.000000026176508e-09
SA1_XTD2_VAC/IPUMP/P10250I 0x6007 5.4000000027087935e-09
SA1_XTD9_VAC/IPUMP/P12120I 0x6007 no data
SA1_XTD2_VAC/IPUMP/P10040I 0x6007 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P12200I 0x6009 5.4000000027087935e-09
SA1_XTD2_VAC/IPUMP/P10170I 0x6007 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P12250I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C11002I
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10702I
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11402I
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C10903I
no channel number defined for {} SA1_XTD9_VAC0
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10602I
SA1_XTD9_VAC/IPUMP/P10500I 0x6009 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11050I 0x6009 5.4000000027087935e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11302I
SA1_XTD9_VAC/IPUMP/P10390I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD2_VAC/IPUMP/P10350I
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11102I
SA1_XTD9_VAC/IPUMP/P12280I 0x6009 5.4000000027087935e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11101I
SA1_XTD9_VAC/IPUMP/P11360I 0x6009 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P11180I 0x6007 1.400000004814217e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10701I
SA1_XTD9_VAC/IPUMP/P12020I 0x6009 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P11040I 0x6009 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P10450I 0x6007 5.4000000027087935e-09
SA1_XTD9_VAC/IPUMP/P11020I 0x6009 8.29999979856666e-09
SA1_XTD2_VAC/IPUMP/P10320I 0x6007 5.099999977886682e-09
SA1_XTD2_VAC/IPUMP/P10160I 0x6009 8.399999806840697e-09
SA1_XTD9_VAC/IPUMP/P10460I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD9_VAC/IPUMP/P10370I
SA1_XTD2_VAC/IPUMP/P10260I 0x6009 4.999999969612645e-09
SA1_XTD9_VAC/IPUMP/P10490I 0x6009 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P11080I 0x6007 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P11120I 0x6007 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P11150I 0x6007 4.999999969612645e-09
SA1_XTD2_VAC/IPUMP/P10290I 0x6007 4.699999944790534e-09
SA1_XTD9_VAC/IPUMP/P11170I 0x6007 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P12150I 0x6007 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P10380I 0x6009 5.099999977886682e-09
no channel number defined for {} SA1_XTD9_VAC2
SA1_XTD9_VAC/IPUMP/P12160I 0x6007 5.099999977886682e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C10902I
SA1_XTD9_VAC/IPUMP/P10400I 0x6009 5.099999977886682e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10102I
SA1_XTD9_VAC/IPUMP/P12210I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11802I
SA1_XTD2_VAC/IPUMP/P10310I 0x6009 3.999999886872274e-09
SA1_XTD9_VAC/IPUMP/P12090I 0x6007 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P12240I 0x6009 8.29999979856666e-09
SA1_XTD2_VAC/IPUMP/P10060I 0x6009 5.099999977886682e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C11004I
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11301I
SA1_XTD9_VAC/IPUMP/P12270I 0x6009 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P11340I 0x6009 8.29999979856666e-09
SA1_XTD9_VAC/IPUMP/P10470I 0x6009 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P11030I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10603I
SA1_XTD2_VAC/IPUMP/P10020I 0x6009 1.2000000992884452e-09
SA1_XTD9_VAC/IPUMP/P12040I 0x6007 1.2000000992884452e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C11003I
no channel number defined for {} SA1_XTD2_VAC/IPUMP/P10360I
SA1_XTD2_VAC/IPUMP/P10210I 0x6009 3.4000000592726565e-09
SA1_XTD9_VAC/IPUMP/P12080I 0x6007 1.2000000992884452e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11702I
SA1_XTD9_VAC/IPUMP/P10420I 0x6007 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P12070I 0x6007 3.4000000592726565e-09
SA1_XTD9_VAC/IPUMP/P11090I 0x6007 5.099999977886682e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10502I
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C11001I
SA1_XTD9_VAC/IPUMP/P12110I 0x6007 3.4000000592726565e-09
SA1_XTD9_VAC/IPUMP/P12050I 0x6007 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P12170I 0x6007 1.400000004814217e-09
no channel number defined for {} SA1_XTD2_VAC
SA1_XTD9_VAC/IPUMP/P10480I 0x6009 3.4000000592726565e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C10801I
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11401I
SA1_XTD9_VAC/IPUMP/P10410I 0x6009 2.5999999930803597e-09
SA1_XTD2_VAC/IPUMP/P10330I 0x6007 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11350I 0x6009 5.099999977886682e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11801I
SA1_XTD9_VAC/IPUMP/P11300I 0x6009 1.2000000992884452e-09
SA1_XTD9_VAC/IPUMP/P11320I 0x6007 1.400000004814217e-09
SA1_XTD2_VAC/IPUMP/P10010I 0x6007 3.5000000675466936e-09
SA1_XTD9_VAC/IPUMP/P11310I 0x6009 5.099999977886682e-09
SA1_XTD9_VAC/IPUMP/P11070I 0x6007 3.5000000675466936e-09
SA1_XTD9_VAC/IPUMP/P12230I 0x6009 3.5000000675466936e-09
SA1_XTD9_VAC/IPUMP/P11100I 0x6007 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P12060I 0x6007 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P12290I 0x6007 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P12130I 0x6007 5.099999977886682e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11701I
SA1_XTD9_VAC/IPUMP/P11060I 0x6009 1.400000004814217e-09
SA1_XTD9_VAC/IPUMP/P11190I 0x6007 2.5999999930803597e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10501I
SA1_XTD9_VAC/IPUMP/P11160I 0x6007 1.2000000992884452e-09
SA1_XTD9_VAC/IPUMP/P12010I 0x6009 5.099999977886682e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10601I
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10703I
SA1_XTD9_VAC/IPUMP/P12030I 0x6007 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P12140I 0x6007 1.400000004814217e-09
SA1_XTD2_VAC/IPUMP/P10240I 0x6007 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P12100I 0x6007 1.400000004814217e-09
no channel number defined for {} SA1_XTD2_VAC/ICTRL/C10101I
SA1_XTD2_VAC/IPUMP/P10050I 0x6009 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11290I 0x6009 2.5999999930803597e-09
no channel number defined for {} SA1_XTD9_VAC/ICTRL/C11202I
SA1_XTD9_VAC/IPUMP/P10440I 0x6007 2.5999999930803597e-09
SA1_XTD9_VAC/IPUMP/P11140I 0x6007 1.400000004814217e-09
SA1_XTD2_VAC/IPUMP/P10190I 0x6007 1.2000000104706032e-08
SA1_XTD9_VAC/IPUMP/P12220I 0x6009 1.2000000992884452e-09
SA1_XTD2_VAC/IPUMP/P10300I 0x6009 5.4000000027087935e-09
  48   15 Feb 2017, 20:20 Alessandro SilenziGeneralFeedbackMotion loop status

The motion loop is as of 18:40 online.

the current status of the devices as seen by the Karabo is shown in the attachment:

In summary 63 devices (29 Motors):

18 in error

- 14 in error 0x8004 (Terminal unavailable)

- 4 in error 0x8003 (Terminal unavailable)

This is the list of motor that are behaving according to karabo

SA1_XTD2_MIRR-2/MOTOR/HMRZ Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_RIGHT Success State.OFF
SA1_XTD2_IMGFEL/MOTOR/SCREEN Success State.OFF
SA1_XTD2_FLT/MOTOR/TARGET Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMRZ Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_LEFT Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMTX Success State.OFF
SA1_XTD2_IMGSR/MOTOR/TARGET_X Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMRX Success State.OFF
SA1_XTD2_IMGSR/MOTOR/IRIS Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMRY Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_BOTTOM Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMRY Success State.OFF
SA1_XTD2_IMGSR/MOTOR/FOCUS Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMTX Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMTY Success State.OFF
SA1_XTD9_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMRX Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_TOP Success State.OFF
SA1_XTD2_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD2_IMGFEL/MOTOR/FILTER Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMTY Success State.OFF
 

Attachment 1: 20170215MotionLoop.txt
SA1_XTD2_MIRR-2/MOTOR/HMRZ Success State.OFF
SA1_XTD9_IMGPII45/DCTRL/CAM_POWER 0x8003
SPB_XTD9_IMGPI/DCTRL/LED_POWER 0x8004
SA1_XTD2_PSLIT/MOTOR/BLADE_RIGHT Success State.OFF
SA1_XTD2_IMGFEL/MOTOR/SCREEN Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMRX Success State.STOPPED
SA1_XTD2_FLT/MOTOR/TARGET Success State.OFF
SA1_XTD2_IMGFEL/DCTRL/LED_POWER Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMRZ Success State.OFF
SA1_XTD2_PSLIT/LVDT/BLADE_RIGHT Success State.NORMAL
SA1_XTD2_PSLIT/MOTOR/BLADE_LEFT Success State.OFF
SA1_XTD9_MIRR/MOTOR/HMTX 0x8003
SA1_XTD2_MIRR-1/MOTOR/HMTX Success State.OFF
SA1_XTD2_IMGSR/MOTOR/TARGET_X Success State.OFF
SA1_XTD9_MIRR/ENC/HMRZ 0x8004
SA1_XTD2_MIRR-2/ENC/HMRY Success State.STOPPED
SA1_XTD9_MIRR/ENC/HMTX 0x8004
SA1_XTD2_MIRR-2/ENC/HMTY Success State.STOPPED
SA1_XTD9_MIRR/MOTOR/HMRY 0x8004
SA1_XTD2_IMGPII45/DCTRL/CAM_POWER Success State.OFF
SA1_XTD2_PSLIT/LVDT/BLADE_BOTTOM Success State.NORMAL
SA1_XTD2_MIRR-2/MOTOR/HMRX Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMTY Success State.STOPPED
FXE_XTD9_IMGPI/DCTRL/CAM_POWER 0x8004
SA1_XTD9_MIRR/MOTOR/HMRZ 0x8004
SA1_XTD2_IMGSR/MOTOR/IRIS Success State.OFF
FXE_XTD9_IMGPI/MOTOR/SCREEN 0x8004
SA1_XTD2_MIRR-1/MOTOR/HMRY Success State.OFF
SA1_XTD2_PSLIT/LVDT/BLADE_TOP Success State.NORMAL
SA1_XTD2_IMGPII45/DCTRL/LED_POWER Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_BOTTOM Success State.OFF
SA1_XTD9_MIRR/ENC/HMTY 0x8004
SA1_XTD2_IMGFEL/SWITCH/DECELERATE Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMRY Success State.STOPPED
SA1_XTD2_MIRR-2/MOTOR/HMRY Success State.OFF
SA1_XTD2_IMGSR/MOTOR/FOCUS Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMTX Success State.OFF
SA1_XTD2_IMGSR/LVDT/Y Success State.NORMAL
SA1_XTD2_MIRR-1/MOTOR/HMTY Success State.OFF
SA1_XTD2_IMGFEL/DCTRL/CAM_POWER Success State.OFF
SA1_XTD9_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD9_IMGPII45/DCTRL/LED_POWER 0x8003
SA1_XTD9_MIRR/ENC/HMRY 0x8004
SA1_XTD9_MIRR/MOTOR/HMRX 0x8004
SA1_XTD2_MIRR-1/ENC/HMRZ Success State.STOPPED
SA1_XTD2_MIRR-1/MOTOR/HMRX Success State.OFF
SPB_XTD9_IMGPI/DCTRL/CAM_POWER 0x8004
SA1_XTD2_PSLIT/LVDT/BLADE_LEFT Success State.NORMAL
SPB_XTD9_IMGPI/MOTOR/SCREEN 0x8004
SA1_XTD9_MIRR/ENC/HMRX 0x8004
SA1_XTD2_MIRR-2/ENC/HMTX Success State.STOPPED
SA1_XTD2_PSLIT/MOTOR/BLADE_TOP Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMTX Success State.STOPPED
SA1_XTD9_MIRR/MOTOR/HMTY 0x8003
SA1_XTD2_IMGSR/DCTRL/CAM_POWER Success State.OFF
SA1_XTD2_IMGSR/DCTRL/LED1 Success State.OFF
SA1_XTD2_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD2_MIRR-2/ENC/HMRZ Success State.STOPPED
SA1_XTD2_IMGSR/DCTRL/PD_POWER Success State.OFF
SA1_XTD2_MIRR-2/ENC/HMRX Success State.STOPPED
SA1_XTD2_IMGFEL/MOTOR/FILTER Success State.OFF
FXE_XTD9_IMGPI/DCTRL/LED_POWER 0x8004
SA1_XTD2_MIRR-2/MOTOR/HMTY Success State.OFF
  49   17 Feb 2017, 09:56 Alessandro SilenziGeneralFeedbackMotion loop feedback

Quick feedback during the meeting:

- 63 Devices

- 29 Motors

Errors only in 

- SPB_XTD9_IMGPI

- FXE_XTD9_IMGPI

Attachment 1: 20170217Motion.txt
SA1_XTD2_MIRR-1/MOTOR/HMRY Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMRZ Success State.STOPPED
SA1_XTD9_MIRR/MOTOR/HMRY Success State.OFF
SA1_XTD2_FLT/MOTOR/TARGET Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_LEFT Success State.OFF
SA1_XTD2_PSLIT/LVDT/BLADE_RIGHT Success State.NORMAL
SA1_XTD2_IMGFEL/MOTOR/FILTER Success State.OFF
FXE_XTD9_IMGPI/DCTRL/CAM_POWER 0x8004
SPB_XTD9_IMGPI/DCTRL/CAM_POWER 0x8004
SA1_XTD9_MIRR/ENC/HMTX Success State.STOPPED
SA1_XTD2_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD9_MIRR/MOTOR/HMRX Success State.OFF
SA1_XTD2_IMGPII45/DCTRL/LED_POWER Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMTY Success State.OFF
SA1_XTD9_IMGPII45/MOTOR/SCREEN Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMRX Success State.OFF
SPB_XTD9_IMGPI/MOTOR/SCREEN 0x8004
SA1_XTD2_IMGSR/DCTRL/LED1 Success State.OFF
SA1_XTD9_MIRR/ENC/HMRX Success State.STOPPED
SA1_XTD2_IMGSR/MOTOR/TARGET_X Success State.OFF
SA1_XTD9_MIRR/MOTOR/HMTY Success State.OFF
SA1_XTD2_IMGSR/DCTRL/PD_POWER Success State.OFF
SA1_XTD2_IMGSR/LVDT/Y Success State.NORMAL
FXE_XTD9_IMGPI/MOTOR/SCREEN 0x8004
SA1_XTD2_IMGFEL/SWITCH/DECELERATE Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMTX Success State.STOPPED
SA1_XTD9_MIRR/ENC/HMTY Success State.STOPPED
SA1_XTD2_MIRR-2/ENC/HMRX Success State.STOPPED
SA1_XTD2_MIRR-2/ENC/HMTY Success State.STOPPED
SA1_XTD2_IMGFEL/MOTOR/SCREEN Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMRY Success State.OFF
SA1_XTD2_MIRR-2/ENC/HMRY Success State.STOPPED
SA1_XTD9_MIRR/ENC/HMRZ Success State.STOPPED
SA1_XTD2_PSLIT/LVDT/BLADE_LEFT Success State.NORMAL
SA1_XTD2_PSLIT/LVDT/BLADE_TOP Success State.NORMAL
SA1_XTD2_PSLIT/MOTOR/BLADE_RIGHT Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMTY Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMRZ Success State.OFF
SA1_XTD9_IMGPII45/DCTRL/CAM_POWER Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMRX Success State.STOPPED
SA1_XTD2_IMGFEL/DCTRL/LED_POWER Success State.OFF
SA1_XTD9_MIRR/MOTOR/HMTX Success State.OFF
SA1_XTD2_IMGSR/MOTOR/IRIS Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_TOP Success State.OFF
SPB_XTD9_IMGPI/DCTRL/LED_POWER 0x8004
SA1_XTD2_MIRR-1/MOTOR/HMRZ Success State.OFF
SA1_XTD2_IMGSR/MOTOR/FOCUS Success State.OFF
FXE_XTD9_IMGPI/DCTRL/LED_POWER 0x8004
SA1_XTD2_MIRR-1/ENC/HMTY Success State.STOPPED
SA1_XTD9_MIRR/ENC/HMRY Success State.STOPPED
SA1_XTD2_MIRR-2/ENC/HMRZ Success State.STOPPED
SA1_XTD2_IMGPII45/DCTRL/CAM_POWER Success State.OFF
SA1_XTD2_MIRR-2/MOTOR/HMTX Success State.OFF
SA1_XTD9_IMGPII45/DCTRL/LED_POWER Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMRX Success State.OFF
SA1_XTD2_PSLIT/LVDT/BLADE_BOTTOM Success State.NORMAL
SA1_XTD2_MIRR-2/ENC/HMTX Success State.STOPPED
SA1_XTD2_IMGSR/DCTRL/CAM_POWER Success State.OFF
SA1_XTD2_PSLIT/MOTOR/BLADE_BOTTOM Success State.OFF
SA1_XTD2_IMGFEL/DCTRL/CAM_POWER Success State.OFF
SA1_XTD9_MIRR/MOTOR/HMRZ Success State.OFF
SA1_XTD2_MIRR-1/MOTOR/HMTX Success State.OFF
SA1_XTD2_MIRR-1/ENC/HMRY Success State.STOPPED
  66   08 Mar 2017, 18:26 Alessandro SilenziGeneralInformationKarabo Deployment Documentation link

Url to the readthedocs documentation:

https://goo.gl/vsz9hu

  69   10 Mar 2017, 11:34 Alessandro SilenziGeneralInformationLink to the redmin list of Tasks.

https://in.xfel.eu/redmine/projects/control-support/issues

Short Instructions:

- Add your task

- Select your work package

- Do NOT set the assignee

- Do NOT set the priority

 

  95   04 Apr 2017, 12:28 Alessandro SilenziGeneralInformationTemperatures from EPS loop

This is the list of data coming directly from the PLC via its TCP client connected to the EPS PLC.

Format:

deviceName  temperature  status errorCode

XTD2

==================================================

SA1_XS3_SHUT/TSENS/T1 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T2 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T3 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T4 0.4000000059604645 0xa020 0x0
SA1_XTD2_ABS/TSENS/T1 0.0 0x20 0x0
SA1_XTD2_ABS/TSENS/T2 0.0 0x20 0x0
SA1_XTD2_ATT/TSENS/A1 30.739999771118164 0x20 0x0
SA1_XTD2_ATT/TSENS/A2 1372.0 0x15020 0x0
SA1_XTD2_ATT/TSENS/A3 30.380002975463867 0x20 0x0
SA1_XTD2_ATT/TSENS/A4 31.05000114440918 0x20 0x0
SA1_XTD2_ATT/TSENS/A6 31.130002975463867 0x20 0x0
SA1_XTD2_ATT/TSENS/A7 30.78000259399414 0x20 0x0
SA1_XTD2_ATT/TSENS/A8 30.98000144958496 0x20 0x0
SA1_XTD2_ATT/TSENS/A9 33.5 0x20 0x0
SA1_XTD2_COLA/TSENS/T1 0.0 0x1020 0x0
SA1_XTD2_COLA/TSENS/T2 0.0 0x1020 0x0
SA1_XTD2_COLB/TSENS/T1 0.0 0x20 0x0
SA1_XTD2_COLB/TSENS/T2 0.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_10_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_10_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_1_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_1_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_2_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_2_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_3_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_3_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_4_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_4_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_5_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_5_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_6_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_6_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_7_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_7_T2 33.5 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_8_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_8_T2 33.5 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_9_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_9_T2 33.5 0x1020 0x0
SA1_XTD2_DPS1/TSENS/FLOW 2.0300002098083496 0x20 0x0
SA1_XTD2_DPS1/TSENS/RETURN1 33.5 0x20 0x0
SA1_XTD2_DPS1/TSENS/RETURN2 2.0200002193450928 0x20 0x0
SA1_XTD2_DPS3/TSENS/FLOW 33.5 0x20 0x0
SA1_XTD2_DPS3/TSENS/RETURN1 4.160000324249268 0x20 0x0
SA1_XTD2_DPS3/TSENS/RETURN2 4.420000076293945 0x20 0x0
SA1_XTD2_PBLM/TSENS/BLADE_LEFT 32.900001525878906 0x20 0x0
SA1_XTD2_PBLM/TSENS/BLADE_RIGHT 33.5 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_W 0.0 0x20 0x0
 

XTD9

============================================================

SA1_XTD9_PBLM/TSENS/BLADE_LEFT 24.31999969482422 0x20 0x0
SA1_XTD9_PBLM/TSENS/BLADE_RIGHT 24.810001373291016 0x20 0x0
SPB_XTD9_COLB/TSENS/T1 0.0 0x20 0x0
SPB_XTD9_COLB/TSENS/T2 0.0 0x1020 0x0
SPB_XTD9_DPS1/TSENS/FLOW 33.5 0x1020 0x0
SPB_XTD9_DPS1/TSENS/RETURN1 85.0 0x1020 0x0
SPB_XTD9_DPS1/TSENS/RETURN2 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/FLOW 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/RETURN1 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/RETURN2 85.0 0x1020 0x0
SPB_XTD9_PBLM/TSENS/BLADE_BOTTOM 23.05000114440918 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_LEFT 22.860000610351562 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_RIGHT 23.05000114440918 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_TOP 23.05000114440918 0x20 0x0
SPB_XTD9_SHUT/TSENS/T1 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T2 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T3 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T4 0.0 0x1020 0x0
FXE_XTD9_COLB/TSENS/T1 0.0 0x20 0x0
FXE_XTD9_COLB/TSENS/T2 0.0 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_BOTTOM 22.780000686645508 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_LEFT 22.8700008392334 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_RIGHT 22.850000381469727 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_TOP 22.93000030517578 0x20 0x0
 

  96   04 Apr 2017, 12:43 Alessandro SilenziGeneralInformationTemperatures from EPS loop

Alessandro Silenzi wrote:

This is the list of data coming directly from the PLC via its TCP client connected to the EPS PLC.

Format:

deviceName  temperature  status errorCode

XTD2

==================================================

SA1_XS3_SHUT/TSENS/T1 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T2 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T3 0.4000000059604645 0xa020 0x0
SA1_XS3_SHUT/TSENS/T4 0.4000000059604645 0xa020 0x0
SA1_XTD2_ABS/TSENS/T1 0.0 0x20 0x0
SA1_XTD2_ABS/TSENS/T2 0.0 0x20 0x0
SA1_XTD2_ATT/TSENS/A1 30.739999771118164 0x20 0x0
SA1_XTD2_ATT/TSENS/A2 1372.0 0x15020 0x0
SA1_XTD2_ATT/TSENS/A3 30.380002975463867 0x20 0x0
SA1_XTD2_ATT/TSENS/A4 31.05000114440918 0x20 0x0
SA1_XTD2_ATT/TSENS/A6 31.130002975463867 0x20 0x0
SA1_XTD2_ATT/TSENS/A7 30.78000259399414 0x20 0x0
SA1_XTD2_ATT/TSENS/A8 30.98000144958496 0x20 0x0
SA1_XTD2_ATT/TSENS/A9 33.5 0x20 0x0
SA1_XTD2_COLA/TSENS/T1 0.0 0x1020 0x0
SA1_XTD2_COLA/TSENS/T2 0.0 0x1020 0x0
SA1_XTD2_COLB/TSENS/T1 0.0 0x20 0x0
SA1_XTD2_COLB/TSENS/T2 0.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_10_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_10_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_1_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_1_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_2_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_2_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_3_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_3_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_4_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_4_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_5_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_5_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_6_T1 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_6_T2 85.0 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_7_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_7_T2 33.5 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_8_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_8_T2 33.5 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_9_T1 33.60000228881836 0x1020 0x0
SA1_XTD2_CRL/TSENS/LENS_9_T2 33.5 0x1020 0x0
SA1_XTD2_DPS1/TSENS/FLOW 2.0300002098083496 0x20 0x0
SA1_XTD2_DPS1/TSENS/RETURN1 33.5 0x20 0x0
SA1_XTD2_DPS1/TSENS/RETURN2 2.0200002193450928 0x20 0x0
SA1_XTD2_DPS3/TSENS/FLOW 33.5 0x20 0x0
SA1_XTD2_DPS3/TSENS/RETURN1 4.160000324249268 0x20 0x0
SA1_XTD2_DPS3/TSENS/RETURN2 4.420000076293945 0x20 0x0
SA1_XTD2_PBLM/TSENS/BLADE_LEFT 32.900001525878906 0x20 0x0
SA1_XTD2_PBLM/TSENS/BLADE_RIGHT 33.5 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_W 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_B4C 0.0 0x20 0x0
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_W 0.0 0x20 0x0
 

XTD9

============================================================

SA1_XTD9_PBLM/TSENS/BLADE_LEFT 24.31999969482422 0x20 0x0
SA1_XTD9_PBLM/TSENS/BLADE_RIGHT 24.810001373291016 0x20 0x0
SPB_XTD9_COLB/TSENS/T1 0.0 0x20 0x0
SPB_XTD9_COLB/TSENS/T2 0.0 0x1020 0x0
SPB_XTD9_DPS1/TSENS/FLOW 33.5 0x1020 0x0
SPB_XTD9_DPS1/TSENS/RETURN1 85.0 0x1020 0x0
SPB_XTD9_DPS1/TSENS/RETURN2 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/FLOW 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/RETURN1 85.0 0x1020 0x0
SPB_XTD9_DPS2/TSENS/RETURN2 85.0 0x1020 0x0
SPB_XTD9_PBLM/TSENS/BLADE_BOTTOM 23.05000114440918 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_LEFT 22.860000610351562 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_RIGHT 23.05000114440918 0x20 0x0
SPB_XTD9_PBLM/TSENS/BLADE_TOP 23.05000114440918 0x20 0x0
SPB_XTD9_SHUT/TSENS/T1 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T2 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T3 0.0 0x1020 0x0
SPB_XTD9_SHUT/TSENS/T4 0.0 0x1020 0x0
FXE_XTD9_COLB/TSENS/T1 0.0 0x20 0x0
FXE_XTD9_COLB/TSENS/T2 0.0 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_BOTTOM 22.780000686645508 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_LEFT 22.8700008392334 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_RIGHT 22.850000381469727 0x20 0x0
FXE_XTD9_PBLM/TSENS/BLADE_TOP 22.93000030517578 0x20 0x0
 

 Now the loop is accessible to Karabo as well with the project SA1_EPS

  101   04 Apr 2017, 18:49 Alessandro SilenziGeneralInformationUPDATE on Temperature sensors for EPS loop

Here are the updated values for the temperature sensors inn the EPS loop.

Now Thermocouples work!

FXE_XTD9_COLB/TSENS/T1 23.1
FXE_XTD9_COLB/TSENS/T2 23.2
FXE_XTD9_PBLM/TSENS/BLADE_BOTTOM 22.94
FXE_XTD9_PBLM/TSENS/BLADE_LEFT 23.0
FXE_XTD9_PBLM/TSENS/BLADE_RIGHT 23.0
FXE_XTD9_PBLM/TSENS/BLADE_TOP 22.98
SA1_XS3_SHUT/TSENS/T1 4.0
SA1_XS3_SHUT/TSENS/T2 4.0
SA1_XS3_SHUT/TSENS/T3 4.0
SA1_XS3_SHUT/TSENS/T4 4.0
SA1_XTD2_ABS/TSENS/T1 19.5
SA1_XTD2_ABS/TSENS/T2 19.6
SA1_XTD2_ATT/TSENS/A1 30.7
SA1_XTD2_ATT/TSENS/A2 1372.0
SA1_XTD2_ATT/TSENS/A3 30.3
SA1_XTD2_ATT/TSENS/A4 31.02
SA1_XTD2_ATT/TSENS/A5 31.96
SA1_XTD2_ATT/TSENS/A6 31.11
SA1_XTD2_ATT/TSENS/A7 30.75
SA1_XTD2_ATT/TSENS/A8 31.0
SA1_XTD2_ATT/TSENS/A9 31.4
SA1_XTD2_COLA/TSENS/T1 1372.0
SA1_XTD2_COLA/TSENS/T2 1372.0
SA1_XTD2_COLB/TSENS/T1 27.8
SA1_XTD2_COLB/TSENS/T2 1372.0
SA1_XTD2_CRL/TSENS/LENS_10_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_10_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_1_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_1_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_2_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_2_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_3_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_3_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_4_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_4_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_5_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_5_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_6_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_6_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_7_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_7_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_8_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_8_T2 850.0
SA1_XTD2_CRL/TSENS/LENS_9_T1 850.0
SA1_XTD2_CRL/TSENS/LENS_9_T2 850.0
SA1_XTD2_DPS1/TSENS/FLOW 20.3
SA1_XTD2_DPS1/TSENS/RETURN1 20.3
SA1_XTD2_DPS1/TSENS/RETURN2 20.1
SA1_XTD2_DPS3/TSENS/FLOW 44.2
SA1_XTD2_DPS3/TSENS/RETURN1 41.6
SA1_XTD2_DPS3/TSENS/RETURN2 44.2
SA1_XTD2_PBLM/TSENS/BLADE_LEFT 32.8
SA1_XTD2_PBLM/TSENS/BLADE_RIGHT 33.7
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_B4C 19.7
SA1_XTD2_PSLIT/TSENS/BLADE_BOTTOM_W 19.4
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_B4C 18.6
SA1_XTD2_PSLIT/TSENS/BLADE_LEFT_W 18.6
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_B4C 19.3
SA1_XTD2_PSLIT/TSENS/BLADE_RIGHT_W 19.2
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_B4C 19.4
SA1_XTD2_PSLIT/TSENS/BLADE_TOP_W 19.4
SA1_XTD9_PBLM/TSENS/BLADE_LEFT 23.68
SA1_XTD9_PBLM/TSENS/BLADE_RIGHT 24.13
SPB_XTD9_COLB/TSENS/T1 22.9
SPB_XTD9_COLB/TSENS/T2 1372.0
SPB_XTD9_DPS1/TSENS/FLOW 850.0
SPB_XTD9_DPS1/TSENS/RETURN1 850.0
SPB_XTD9_DPS1/TSENS/RETURN2 850.0
SPB_XTD9_DPS2/TSENS/FLOW 850.0
SPB_XTD9_DPS2/TSENS/RETURN1 850.0
SPB_XTD9_DPS2/TSENS/RETURN2 850.0
SPB_XTD9_PBLM/TSENS/BLADE_BOTTOM 23.21
SPB_XTD9_PBLM/TSENS/BLADE_LEFT 23.01
SPB_XTD9_PBLM/TSENS/BLADE_RIGHT 23.19
SPB_XTD9_PBLM/TSENS/BLADE_TOP 23.12
SPB_XTD9_SHUT/TSENS/T1 1372.0
SPB_XTD9_SHUT/TSENS/T2 1372.0
SPB_XTD9_SHUT/TSENS/T3 1372.0
SPB_XTD9_SHUT/TSENS/T4 1372.0

 

  116   07 Apr 2017, 16:02 Alessandro SilenziGeneralInformationTest on Karabo trunk show promising results

I have deployed the Karabo master (the HEAD of our development) in the control network for the Vacuum loop device server.

During last weeks Karabo was not able to cope with the data coming from the PLC for this loop (our biggest to date)
and would become unresponsive after 5 to 10 minutes.

The current system is online since 3.5 hours and is still responsive.

Please note:
This is a partial release and the GUI might show unwanted behaviour.
Please leave the vacuum loop untouched during the weekend.

In attachment you can find an example of unwanted behaviour and the DPS gui

Thank you very much and have a nice weekend!

Alessandro

Attachment 1: 02.png
02.png
Attachment 2: 12.png
12.png
  124   10 Apr 2017, 12:31 Alessandro SilenziGeneralInformationKARABO Update maintainance

The karabo services will be down for an upgrade for an hour.

The access will resume at 13:30.

  132   11 Apr 2017, 13:48 Alessandro SilenziGeneralInformationScript to install the latest karabo

Please find in attachment the dowload bash script for the latest Karabo.

if your system has a "karabo" directory, this script will not overwrite it, but the update will fail.
In this case, remove or rename the karabo directory.

To use it:
1. download the script in a directory of your choice.

2. open a terminal and execute it with
   $ bash PATH_TO/download.sh

Where PATH_TO is the path where the download script was saved.

Attachment 1: download.sh
#!/bin/bash

if [ -z ${outfilename} ]
then
    outfilename=.karabo.sh
fi
echo $outfilename
git clone https://xfel.redmine:K9Sss5CmWtQ_nbx3gyt2@git.xfel.eu/gitlab/Karabo/commissioning-guidelines .temp-commissioning --depth=1
cp -f .temp-commissioning/project_generation/install.sh .install.sh
rm -fr .temp-commissioning
. .install.sh
rm ${outfilename}
rm .install.sh
  141   13 Apr 2017, 10:15 Alessandro SilenziGeneralProblemEtherCAT loop broken for Vacuum loop

The EtherCAT loop for the vacuum PLC is interrupted at crate 1.6 (XTD2).

This triggered all Beckhoff Terminals  default behaviour from this point on (i.e. Valves Closed, Digital Outputs low, etc.).

 

 

  201   03 May 2017, 12:32 Alessandro SilenziGeneralInformationGUI Server redeployment

The GUI server has been redeployed and a second one has been added.

In order to access those:

please log out of the gateway and log in again using the usual command

ssh desyusername@exflgateway -L 44444:sa1-br-sys-con-gui1:44444

or

ssh desyusername@exflgateway -L 44444:sa1-br-sys-con-gui2:44444