ID |
Date |
Author |
Location |
Severity |
Subject |
27
|
26 Jan 2017, 17:02 |
Tobias Haas | XTD2 | Problem | XGM at XTD2 / issue with in-vacuum-resistor | Post on behalf of Jan Grünert:
during HV-tests on the installed XGMs, our DESY colleagues from Kai Tiedtkes team have found an issue with one of the electrodes / resistors inside one XGM vacuum chamber at XTD2.
Roughly, we know the following:
1) If not repaired, we would lose at least the capability of monitoring shot-to-shot horizontal beam position at this XGM location. This is a lower-priority info.
2) However, it’s not yet fully tested if other functionalities could be affected. In case the absolute calibrated intensity info is affected, then clearly we would have to repair.
3) Since the cause of the resistor-irregularity is not understood, there is a risk to damage the other (operational) remaining resistors in the other chambers of the same XGM.
It is not yet fully clear
a) what is the cause for the irregular behavior (it concerns a resistor inside vacuum which dramatically changed its resistance, which apparently possibly might happen even during a correct dry-nitrogen venting),
b) the entire consequences for operation with this XGM
c) the effort/details of a potential repair (could include up to removing one of the four chambers off the girder out of the tunnel into a lab, certainly needs re-survey)
d) if another XGM chamber is affected (so far tested 2 of 6).
The DESY colleagues are running various tests with us on the XGMs, also extending to all the other XGMs, to get answers to the above questions in order to allow a decision on “repair/not repair”.
Since this concerns the internals of the high-prio XGM in XTD2, we could ask Kai Tiedtke to give us his brief 10min report and recommendation in the tomorrow SASE1Readiness Meeting. Should we request his presence / will you add him to the agenda ?
Best regards,
Jan
________________________________________
Dr. Jan Grünert
Group Leader X-ray Photon Diagnostics (WP74)
European XFEL GmbH
Holzkoppel
|
31
|
01 Feb 2017, 17:42 |
Jan Grünert | General | Problem | XGM resistor issue - analysis progress | This is the current (w5) progress at DESY concerning the analysis of the serious XGM resistor issue (summary; a detailed report by DESY is available):
- The new “pulser test” was verified at an operational XGMD at FLASH. The test method is (unfortuately) OK. This means that the test results with issues from last week on all our XGMs are REAL.
- 25% of all resistors in XBPMs affected, 0% of resistors in HAMPs affected, no capacitors affected.
- Since no HAMP resistors are damaged, damage by environmental conditions (venting, humidity etc.) can be excluded. The main differences to the affected resistors are the HV-conditioning and the experienced HV-values of the resistors (typically XBPM resisotors are tested up to 12kV, HAMP resistors each see much lower voltages).
- An XGMD chamber at FLASH was tested-to-destruction-of-resistor by applying a large differential voltage (>3kV) between neighboring electrodes, e.g. on mesh_e and FC_e. These resistors (Caddock MS220) have a nominal voltage breakthrough rating of ~500V but never had issues. They are used in all our XGMs.
- New, other resistors (Ohmite MOX-1N-13) with higher voltage breakthrough rating of 10kV were procured and arrived tuesday
- The new resistors were built into the tested-to-destruction XGMD at FLASH, unit is now pumping, will be retested with applying pulsed HV (on both Caddoc and Ohmite resistors) when at suitable pressure.
Further plan (w5end + w6) concerning the XGM resistor issue:
- If the new resistors survive the test, then next monday the XGM01 at HERA-S will be opened, the tested-defect resistors will be checked and replaced with the new resistors.
- If all tests on XGM01 are then ok including an acceptable RGA, all other XGMs (XBPM chambers) will be opened and resistors exchanged. Even ok-tested resitors would be exchanged to avoid future unexpected failures. HAMP chamber resistors will not be exchanged (large number >20 of resistors, no failures).
- If the RGA is not acceptable, the resistor Ohmite MOX-1N-16 is another alternative, but has increased delivery time.
|
45
|
12 Feb 2017, 14:02 |
Alessandro Silenzi | General | Problem | Current Status | Vacuum loop:
- Interface between PLC and Karabo is not functioning.
The fault currently resides in the PLC behaviour, the self-description sent out is badly formatted (due to a buffer overrun)
The misbehaviour is confirmed, the PLC TCP Client from AE is also ailed by the same problem.
Motion Loop:
- As of Friday, the motor parameters were not completely sent to AE. In attachment the data collected by N. Jardon (AE). Input needed for PSLIT motors.
|
46
|
14 Feb 2017, 09:59 |
Alessandro Silenzi | General | Problem | Beckhoff loop status | 2017.02.13 19:30 Status:
- Self-Description back in shape.
- Bad SelfDescription reproduced in BeckhoffSim (Karabo implemented PLC communication) and solved in BeckhoffCom (Karabo "PLC Client").
- The build status of the Firmware is not ok. roughly 90% of the PLC soft devices are in error. It is a fault in the automatic Firmware build procedure.
Nerea and Jan will work on this until it is fixed.
|
64
|
08 Mar 2017, 16:08 |
Andreas Koch | XTD2 | Problem | Karabo testing | End switch testing: the in-position end switch stopped devices working, also stopped gateway connection. Stroke of motor is not correct, parameter list to be checked. More details in "Improvements / bug list". |
133
|
11 Apr 2017, 15:24 |
Jan Grünert | XTD2 | Problem | Big issue with XGM vacuum in both XTD2 and XTD9 ! |
Both XGMs were and are on manual control (but the remote cables into the turbo pump controllers remained plugged in as usual) = both XGMs are "out of the VAC loop".
In XTD2, I saw around 13h that both turbos were off (0 Hz) and the pressure was at 10E-4 mbar !
The green light above the ON-button was flickering.
I switched parameter 023 (Motor TMP) to ON and restarted both pumps. The green light above the ON-button
stops flickering and goes steady green.
---going to XTD9
In XTD9, I saw that the upstream turbo was off (0 Hz) and the pressure was in the lower 10E-6mbar.
The downstream turbo in XTD9 was still operating.
Parameter 023 to ON, and restart pump.
---going to XTD2
Error codes 6, 6, 98, 2, 37 on one pump, error codes 6,6,6 on the other (XTD2).
I unplugged the REMOTE cables in XTD2 and XTD9 to avoid further trouble as long as we are on "manual".
This info was also sent by email to the involved experts.
|
141
|
13 Apr 2017, 10:15 |
Alessandro Silenzi | General | Problem | EtherCAT loop broken for Vacuum loop | The EtherCAT loop for the vacuum PLC is interrupted at crate 1.6 (XTD2).
This triggered all Beckhoff Terminals default behaviour from this point on (i.e. Valves Closed, Digital Outputs low, etc.).
|
156
|
21 Apr 2017, 12:28 |
Raúl Villanueva-Guerrero | XTD9 | Problem | FAILED - Interlock test of the whole gas section in XTD9 - NOT SUCCESSFUL | Due to problems and lack of support of CAS for accessing the devices in XTD9 tunnel through KARABO we couldn´t run the test. The system has been returned to manual operation and will remain like that until next notice.
|
157
|
21 Apr 2017, 13:23 |
Raúl Villanueva-Guerrero | XTD9 | Problem | FAILED - Interlock test of the whole gas section in XTD9 - NOT SUCCESSFUL |
Raúl Villanueva-Guerrero wrote: |
Due to problems and lack of support of CAS for accessing the devices in XTD9 tunnel through KARABO we couldn´t run the test. The system has been returned to manual operation and will remain like that until next notice.
|
As soon we received the request we worked on that one. After analysing the issue proper response was sent.
----- Forwarded Message -----
From: "Wajid Ehsan" <wajid.ehsan@xfel.eu>
To: "Raul Villanueva" <raul.villanueva@xfel.eu>
Cc: "Alessandro Silenzi" <alessandro.silenzi@xfel.eu>, "Nerea Jardon" <nerea.jardon@xfel.eu>
Sent: Friday, 21 April, 2017 12:56:14
Subject: Re: Karabo problems in XTD9 - Urgent!
Hi Rahul,
we checked all the devices that are in error. The issue is realted with hardware.
Error description is mentioned below:
0x1001 FlagCtrl Error flag from controller
Regards,
Wajid Ehsan
|
158
|
21 Apr 2017, 13:35 |
Raúl Villanueva-Guerrero | XTD9 | Problem | FAILED - Interlock test of the whole gas section in XTD9 - NOT SUCCESSFUL |
Raúl Villanueva-Guerrero wrote: |
Raúl Villanueva-Guerrero wrote: |
Due to problems and lack of support of CAS for accessing the devices in XTD9 tunnel through KARABO we couldn´t run the test. The system has been returned to manual operation and will remain like that until next notice.
|
As soon we received the request we worked on that one. After analysing the issue proper response was sent.
----- Forwarded Message -----
From: "Wajid Ehsan" <wajid.ehsan@xfel.eu>
To: "Raul Villanueva" <raul.villanueva@xfel.eu>
Cc: "Alessandro Silenzi" <alessandro.silenzi@xfel.eu>, "Nerea Jardon" <nerea.jardon@xfel.eu>
Sent: Friday, 21 April, 2017 12:56:14
Subject: Re: Karabo problems in XTD9 - Urgent!
Hi Rahul,
we checked all the devices that are in error. The issue is realted with hardware.
Error description is mentioned below:
0x1001 FlagCtrl Error flag from controller
Regards,
Wajid Ehsan
|
Here is the list of devices that are in error:
SA1_XTD9_VAC/VALVE/V11090A Error 3 -> valve stayed between open and closed for too long time (3s set on the valve) (the reset command is sent to the PLC and it cannot clear the error)
SA1_XTD9_VAC/VALVE/V11100A Error 3 -> valve stayed between open and closed for too long time (3s set on the valve)
SA1_XTD9_VAC/VALVE/V11110A Error 3 -> valve stayed between open and closed for too long time (3s set on the valve)
SA1_XTD9_VAC/TPUMP/P11220T Error 0x1001 -> err_FlagCtrl -> Error flag from controller (need manual reset on the controller) after reset error is now cleared.
SA1_XTD9_VAC/TPUMP/P11280T Error 0x1001 -> err_FlagCtrl -> Error flag from controller (need manual reset on the controller) after reset error is now cleared.
SA1_XTD9_VAC/VALVE/V11210G Error 0x10001 -> _err_InterlockDevNotFound -> Interlock device not found. (the valves depends from a SA1_XTD9_VAC/SWITCH/DP_XGM_DP_ERROR which does not exist. a SA1_XTD9_VAC/SWITCH/DP_XGM_DP_OK is present in the list though, likely a PLC configuration error).
SA1_XTD9_VAC/VALVE/V11220G Error 0x10001 -> _err_InterlockDevNotFound -> Interlock device not found.
For the last 2 errors, which are the only one that have a clear PLC problem, I created a bug report in the redmine project of AE.
https://in.xfel.eu/redmine/issues/16510
Cheers
Alessandro Silenzi |
159
|
21 Apr 2017, 13:54 |
Jan Tolkiehn | General | Problem | Access to control PC | exflplcgwSA1 seems not reachable. This inhibits support for the PLC systems. |
172
|
26 Apr 2017, 10:51 |
Jan Grünert | XTD2 | Problem | karaboGUI issues - during cycling of PLC loop (shutdown and restart) - effects on XGM XTD2 and XTD9 |
Problems described in detail below (this entire procedure takes way too much of our time, effectively still nearly 2 hours!):
Nerea/AE requested yesterday afternoon to shutdown and restart the SASE1 VAC PLC loop once again. We start today morning (wednesday) at 8h30.
8h30
karabo is not showing status of all devices, see three screenshots (attached). karabo-GUI issue.
These devices have to be shutdown and reinstantiated to show a status and to operate them.
Several valves and gauges and scroll pumps affected both in XGM of XTD2 and XTD9.
9h00 finally I can close all four vatterfly valves
9h15 Nerea shuts down and restarts the SASE1 VAC PLC loop
9h25 still waiting for karabo to reconnect to Beckhoff PLC (I cannot do anything in karabo, and
no current status updates of anything)
9h40 SPB_XTD9_XGM scene has loaded (seems like at least). I start the reactivation procedure (switch
on scroll, open valves etc.). Need to reinstantiate several devices.
10h00 SPB_XTD9_XGM: reinstantiate both turbo pumps, CRemotePriority ON, COn, CPump (if CRemotePriority
not visible, again reinstantiate)
READ ADriveCurrent, ARPMIn several times, both should change from time to time, don't
worry about "0" every second read time
10h05 SA1_XTD2_XGM: reinstantiate both turbo pumps, StartPumpingStation
READ ADriveCurrent, ARPMIn several times, both should change from time to time, don't
worry about "0" every second read time
10h10 READ the actual value of the gauges in configurator (not to trust value shown in scene)
10h15 observe DOOCS RVC300 UHV pressures, open vatterfly valves
10h20 end of intervention
|
178
|
26 Apr 2017, 18:34 |
Jan Grünert | XTD9 | Problem | SA1-VAC loop down (only XTD9) and later restarted | Since around 17h30 all XTD9 VAC loop is in error. It came back in karabo around 17h50. XTD2 not affected.
At that point, we had to reset every single karabo device of the XGM, then restart pumps etc.
Did the same also for the DPS upstream and downstream of XGM@XTD9.
XGM vatterfly valves will be opened by me only when I see that no further errors occur.
Currently, all but one pumps were restarted, also in Rauls DPS, only one of these not |
180
|
27 Apr 2017, 07:04 |
Raúl Villanueva-Guerrero | XTD2 | Problem | XTD2 Differential Pumping completely OUT OF OPERATION! | Dear all,
I just checked the Karabo Scene for both XTD9 and XTD9, finding out the not-so-nice situation where all the valves and pumps were respectively closed and stopped. What really worries me is again the fact that these situations are happening without aparent reason. I´m right now trying to start the system remotely but obviously one needs again to access the tunnel for that is the only reason to actually be sure that everything is up an running normally again.
|
181
|
27 Apr 2017, 07:11 |
Raúl Villanueva-Guerrero | XTD2 | Problem | XTD2 Differential Pumping completely OUT OF OPERATION! |
Raúl Villanueva-Guerrero wrote: |
Dear all,
I just checked the Karabo Scene for both XTD9 and XTD9, finding out the not-so-nice situation where all the valves and pumps were respectively closed and stopped. What really worries me is again the fact that these situations are happening without aparent reason. I´m right now trying to start the system remotely but obviously one needs again to access the tunnel for that is the only reason to actually be sure that everything is up an running normally again.
|
UPDATE:
XTD2
The Upstream sector is back into operation.
The Downstream one is still out of order since the turbopumps are whether in error or in an unknown/un-instantiated status.
XTD9
Upstream sector is back to full operation
Downstream sector: only one of the turbos is running. The other one P11280T cannot be reset
Right now that is the only thing I can do.
|
197
|
02 May 2017, 20:11 |
Jan Grünert | XTD2 | Problem | XGM scenes/devices offline - UHV pressures increasing - Please respond now !! | All devices went into unknown state in the karabo XGM scenes in XTD2 and XTD9 at 19h52.
Pressures INCREASE since then (as measured/shown in DOOCS):
XTD2: 2,5E-7mbar and rising
XTD9: 7,7E-7mbar and rising
Please respond now !! We are still in but want to go home ! |
198
|
02 May 2017, 22:27 |
Jan Grünert | XTD2 | Problem | XTD9 vacuum now ok, but not in XTD2: turbos on XGM@XTD2 still in ERROR | Wajid and Leonce from CAS have managed to get us the karabo controls back.
We have now put the XGM@XTD9 back into normal vacuum operation, and opened finally the vatterfly valves, this one is ok, and we checked also the entire XTD9 gas section to be ok.
However, in XGM@XTD2, both XGM turbo pumps are still in ERROR and we cannot get them out - it is an error on the PLC level ? It's something we have not seen before.
The vacuum is at a controlled level of 5E-7mbar thanks to interlock-closed vatterflys.
Request to AE: tomorrow morning, we must remotely get the two turbos out of error (PLC client ?), otherwise we have to request a ZZ access to the tunnel XTD2 for local intervention on the turbo pump controllers.
Request to the AE+CAS group leaders: apparently we need to organize OCD also during nights on weekdays.
|
207
|
04 May 2017, 19:40 |
Jan Grünert | General | Problem | Slow loading in karabo GUI | The current slow response times in the karabo GUI are the following (some measured times for reference):
- opening a project from the project manager : 45sec (just loading, not yet touching any device or scene)
- opening a scene and receiving the status for all devices e.g. XGM@XTD2 : between 90 and 120 sec
- beyond that, it's never clear if the displayed gauge values are true/actual and must be separately read.
- reading explicitly a gauge value (with command READ in configurator) gives currently an updated value after about 10 sec (should be almost immediate when requested)
-----> working with this (getting actual work done) is practically almost impossible
- this is using the "new" gui server "sa1-br-sys-con-gui2"
- this is after 19h30 (shouldn't less traffic help the performance ?)
|
217
|
10 May 2017, 13:03 |
Jan Grünert | XTD2 | Problem | karabo Beckhoff link not reestablished for SASE1 tunnel VAC loop | Could somebody please re-establish the karabo controls of the SASE1 tunnel VAC loop (connection with Beckhoff server) ?
The karabo devices for XGM vacuum XTD2 and XTD9 are still all in UNKNOWN STATE.
We urgently would like to check the XGM vacuum status and restart the pumps before they are vented.
Thanks,
Jan |
218
|
10 May 2017, 13:07 |
Jan Grünert | XTD2 | Problem | karabo Beckhoff link not reestablished for SASE1 tunnel VAC loop |
Jan Grünert wrote: |
Could somebody please re-establish the karabo controls of the SASE1 tunnel VAC loop (connection with Beckhoff server) ?
The karabo devices for XGM vacuum XTD2 and XTD9 are still all in UNKNOWN STATE.
We urgently would like to check the XGM vacuum status and restart the pumps before they are vented.
Thanks,
Jan
|
Jan,
We are working on it. |
|