|  Tunnel closed today. Might re-open around 14:00 Note that that we re-convene briefly at 17:00 today in MCR (Mock-up Control Room) Vacuum Loop: Status: 
    Large number of ion pumps not responding properly (2 in XTD2, 63 in XTD9). There is the suspicion that the parameters on some ion pump controllers might be set incorrectly, such as baud rate or the bus address. The generated error code indicates a bad address.Test in the lab requires Ion pump controller and PCL. No setup currently readily available. Check in the tunnel required. Could take place between 1200 and 1300 in XTD2 with a ZZ. (Update: B. Racky thinks she will be done around 1400 and would prefer access after this time)Preparations needed to include XGM  EPS Loop: Status: 
    Temperature sensors return null value. Suspected firmware bug has been fixed and EPS loop updated by TFEPS to MPS interface requires testing. Should be done tomorrow Motion Loop: Status: 
    Fixes have been applied to the MC2 lib. Tested for TECHNOSOFT driver. Should now work also for PBLMs . Tests do be done starting Wednesday Imagers Status: 
    Camera driver for SR imager not workingCamera driver for FEL driver working for imager in XTD2 but not for XTD9 Tasks for today: 
    E. Eidam, V. Bondor, , J. Tolkiehn H. Sinn go through all ion pumps in the Silenzi listE. Eidam, T. Freyermuth check pump controller settings in the tunnelA. Koch and W. Ehsan work on Photonics Camera driver for FEL imager   Tasks for tomorrow: 
    M. Planas, T. Maltezopoulos, N. Jardon, J. Eidam test XGM vacuum integration in XTD2 (not XTD9)N. Gerasimova, N. Gerasimova and 1 firmware expert test PBLMs in the tunnelT. Freyermuth tests EPS -> MPS interface   Other topics 
    The two signals from MCP to EPS shall be called MCP-upstream and MCP-downstream               |