Group Selection Page HELP Controls Group ITDM DET Vacuum WP78 FXE SPB HED SQS SXP Sample Environment PSPO XO TS Migrated2Zulip Archived2GitlabPages Archived2PDF MigratedByGroup
WP76 EEE DET_archived DET_deleted
General electronics MicroTCA EEE Electronics Lab EEE Rack Room
  MicroTCA Logbook  Not logged in ELOG logo
Message ID: 151     Entry time: 02 Oct 2014, 10:35
Author: Frank Babies 
Type: Configuration 
Category: N.A.T. MCH 
Subject: base configuration from the MCH 

INFO - MCH configuration CFG V2.14 for V2.14.1 Final (15:39:47 Jul 25 2013) ok

MCH global parameter:
---------------------
remote interfaces:
  RMCP access:                         enabled
  telnet access:                       enabled
  WEB access:                          enabled
IP address source Mgmt:                board configuration
RMCP session activity timeout minutes: 0 min
RMCP session activity timeout seconds: 60 sec
default fan level:                     30 percent
MCH configuration flags:
  Enable backward compatibility V2.4:  no
  Enable alternative cooling scheme:   no
  Control rear transition module fans: no
  Enable Telnet inact timeout (600s):  no

Shelf manager parameter:
------------------------
ShM configuration flags:
  allow shelf FRU invalid:             yes
  temperature management:              enabled
  emergency shutdown on critical ev.:  disabled
  emergency shutdown on non recov ev.: disabled
  send SEND_MSG confirmation to SMS:   no
  use external shelf manager:          no

Carrier manager parameter:
--------------------------
carrier number default:                0
quiesced event timeout:                10 sec
CM configuration flags:
  allow carrier FRU invalid:           yes
  overrule carrier FRU:                no
  shutdown system if MCH goes down:    no
  enable Clock E-keying:               no

CM debug:
  IPMI:                                disabled
  FRU:                                 disabled
  E-keying:                            disabled
  sensor:                              disabled
  event:                               disabled
  power module:                        disabled
  cooling unit:                        disabled
  CM/ShM interface:                    disabled
  debugging FRU:                       0

SEL parameter:
--------------
SEL configuration flags:
  'keep on read':                      disabled
  allocate SEL in non-volatile RAM:    yes
  ignore 'version change' sensor:      yes

Ethernet switch parameter:
--------------------------
 configuration source:  load from FLASH
 ignore backplane FRU info:            no

CLK module parameter:
---------------------
 CLK module configuration source:      load from FLASH

PCIe parameter:
---------------
PCIe Virtual Switch configuration
change via web-interface
 VS # | Host | NT-Host | AMC1 AMC2 AMC3 AMC4 AMC5 AMC6 AMC7 AMC8 AMC9 AMC10 AMC11 AMC12
  0     01     none        X    X    X    X    X    X    X    X    X    X     X     X
  1
  2
  3
  4
  5
Upstream slot power up delay:          15 sec
PCIe power up delay for AMC:           10 sec
PCIe configuration flags:
  100 MHz spread spectrum:             disabled
  hot plug support:                    enabled
  PCIe early ekey (before payload):    enabled
  PCIe clustering:                     enabled

NTP parameter:
--------------
NTP server IP:                         131.169.40.65
NTP 'check for time' delay minutes:    0 min
NTP 'check for time' delay hours:      0 h
NTP local time offset:                 2 h
NTP configuration flags:
  NTP client:                          enabled
  NTP client protocol:                 Time Protocol

DHCP Configuration:
-------------------
host name:                             <empty>
flags:                                 0x00
 

ELOG V3.1.4-7c3fd00